SCHRACK General Purpose Relays Safety Relay on DIN-rail SR6 Z n 6 pole 8 A n SR6 on printed circuit board n AC / DC input n Screwless clamp connectors n Module width 46 mm Applications Elevator control, machine control F0238-C Contact data Terminal assignment Contact set single contact, forcibly guided type A according to EN50205 Rated voltage / max. switching voltage AC 250 VAC / 250 VAC Rated current / limiting continuous current 8A Maximum breaking capacity AC 2000 VA Contact material AgSnO2 Minimum contact load 10 mA / 5 V Contact resistance w100 mOhm / 1 A / 24 VDC w20 Ohm / 10 mA / 5 VDC Rated frequency of operation with / without load 6 min-1 / 150 min-1 DC module, 4 NO+2 NC version S0422-BA Coil data DC energizing voltage Urtd 6, 12, 18, 21, 24, 36, 40, 48, 60, 115 VDC AC/DC energizing voltage Urtd 12, 21, 24, 40, 48, 60,115 VAC/VDC AC energizing voltage Urtd 230 VAC Input circuit bridge rectifier, series resistor Minimum operate voltage, % of rated coil voltage 90% Minimum release voltage (+23C), % of rated coil voltage 10% Limiting voltage, % of rated coil voltage 110% DC module, 3 NO+3 NC version Insulation Surge voltage resistance coil-contacts open contact circuit adjacent contacts Clearance / creepage coil-contact adjacent contacts Insulation to IEC 60664 Voltage rating Pollution degree Overvoltage category 3000 Vrms 1000 Vrms 2000 Vrms W 5.5 / 5.5 mm W 3 / 3 mm S0422-BB DC module, 5 NO+1 NC version 250 V 2 III S0422-BC AC/DC module, 4 NO+2 NC version AC/DC module, 3 NO+3 NC version AC/DC module, 5 NO+1 NC version S0422-BD S0422-BE S0422-BF 1 Datasheet Rev. IJ1 Issued 2009/10 www.tycoelectronics.com www.schrackrelays.com Dimensions are in mm unless otherwise specified and are shown for reference purposes only. Product specification according to IEC 61810-1. Product data, technical parameters, test conditions and processing information only to be used together with the 'Definitions' section in the catalogue or at schrackrelays.com in the `Schrack' section. Specifications subject to change. SCHRACK General Purpose Relays Safety Relay on DIN-rail SR6 Z (Continued) Other data 10x106 cycles Mechanical endurance Material RoHS - Directive 2002/95/EC Environment Ambient temperature Processing Connections (according IEC) solid wire stranded wire AWG Installation position Mounting Type of connection Relay weight Packaging unit compliant -25...+50 C 0.2...2.5 mm2 0.2...2.5 mm2 28...14 any in rows with zero spacing screwless clamp connectors 90 g 2 pcs Dimensions Module width 46 mm Module length 87 mm Fit onto mounting rails according to DIN EN 50022 or DIN EN 50035 S0423-A Product key Typical product key SR6Z A 524 Type SR6Z Safety Relay on DIN-rail SR6 Z Contact configuration A 3 NO + 3 NC contacts (3 form A + 3 form B) B 4 NO + 2 NC contacts (4 form A + 2 form B) C 5 NO + 1 NC contacts (5 form A + 1 form B) Coil DC Coil code = rated coil voltage (e.g. 024=24 VDC) AC/DC coil code: 524=24 VAC/VDC, 615=115 VAC/VDC AC coil code: 730=230 VAC Other types on request Product key SR6ZA024 SR6ZA524 SR6ZA615 SR6ZA730 SR6ZB024 SR6ZB524 SR6ZB615 SR6ZB730 SR6ZC024 SR6ZC524 SR6ZC615 SR6ZC730 Type 6-pole safety relay module Contact configuration 3 NO + 3 NC contacts Contact material AgSnO2 4 NO + 2 NC contacts 5 NO + 1 NC contacts Coil 24 VDC 24 VAC/VDC 115 VAC/VDC 230 VAC 24 VDC 24 VAC/VDC 115 VAC/VDC 230 VAC 24 VDC 24 VAC/VDC 115 VAC/VDC 230 VAC Part number 7-1415033-1 9-1415059-1 1415060-1 1-1415060-1 5-1415033-1 2-1415060-1 6-1415046-1 3-1415060-1 3-1415042-1 4-1415060-1 5-1415060-1 6-1415060-1 2 Datasheet Rev. IJ1 Issued 2009/10 www.tycoelectronics.com www.schrackrelays.com Dimensions are in mm unless otherwise specified and are shown for reference purposes only. Product specification according to IEC 61810-1. Product data, technical parameters, test conditions and processing information only to be used together with the 'Definitions' section in the catalogue or at schrackrelays.com in the `Schrack' section. Specifications subject to change.